Ukukhetha izesekeli zekhebula lamandla ngaphansi kuka-35kV

Ungazi yonke imikhiqizo emisha eshicilelwa lapha, futhi ubone ukukhula kwethu kanye nokusungula izinto ezintsha.

Ukukhetha izesekeli zekhebula lamandla ngaphansi kuka-35kV

Usuku: 09-17-2021

1. I-Teminology
1.1 Ulayini wekhebula
Lonke uhlelo lwakhiwe ngamakhebula, izesekeli, imishini esekelayo kanye nezinsiza ezisekelayo.
1.2 Izesekeli zekhebula
Amatheminali ekhebula, amajoyinti kanye namabhokisi okucindezela ikhebula agcwele uwoyela kubizwa ngokuthi izesekeli zekhebula;

1.3 Imishini yokwengeza ikhebula
Igama elihlanganisiwe lezingxenye zesekethe yekhebula njengebhokisi lokuxhumana eliwela, ibhokisi lokumisa, isivikelo sengqimba yokuvikela, kanye nohlelo lokuqapha;
1.4 Izinsiza ezihambisana nekhebula
Igama elijwayelekile lezingxenye zezintambo zekhebula ezifana namapayipi ekhebula, amabhulokhi, amabhuloho nezakhiwo.
Isendlalelo sezikhali esingu-1.5
Isembozo esakhiwe ngetheyiphu yensimbi noma ucingo. Ngokuvamile sisetshenziselwa ukuvikela ikhebula emandleni angaphandle omshini.
1.6 Ukuphela kwekhebula
Eyaziwa nangokuthi ikhanda lekhebula, iyidivayisi efakwe ekugcineni kwekhebula ukuxhuma ikhebula neminye imishini kagesi noma imigqa yokudlulisa engenhla nokugcina ukufudumala kuze kube yilapho kuxhuma.

1.7Isixhumi sekhebula
Idivayisi exhumanisa umqhubi, ukuvikela, ungqimba lokuvikela kanye nongqimba lokuvikela lwekhebula kukhebula ukuze intambo yekhebula iqhubeke.
1.8 Isihlangu sensimbi
Yakhiwe ngebhande lensimbi elilodwa noma ngaphezulu, amabhande ensimbi, izendlalelo ezigxilile zezintambo zensimbi, noma isakhiwo esihlanganisiwe sezintambo zensimbi namabhande ensimbi.
2. Ukukhethwa kwezesekeli zekhebula
2.1 Ukwakheka kwekhanda lekhebula
Ngokombono wezintambo ezinezinsika ezintathu, izesekeli zekhebula zifaka phakathi amakhanda amathathu esiphelo ancibilikayo abandayo, isikhongozeli esisodwa seminwe emithathu esincibilikayo abandayo, ama-sheath amathathu ancibilikayo abandayo (noma amashubhu okuvikela ancibilikayo abandayo), amashubhu amathathu okuvala ancibilikayo abandayo, kanye nocingo olulodwa lomhlabathi oluphansi.

 

2.2 Ukuhlukaniswa kwamakhanda ekhebula
Ngokusho kwe-voltage yokusebenza, ihlukaniswe phakathi: 1kV, ikhanda lekhebula elingu-10kV, ikhanda lekhebula elingu-35kV;
Ngokwemibandela yokusebenzisa, ihlukaniswe yaba: ama-terminal angaphandle, ama-terminal angaphakathi, kanye nezixhumi eziphakathi;
Ngokwenani lama-core ekhebula, ihlukaniswe yaba: i-terminal enomgogodla owodwa, i-terminal enomgogodla omithathu, i-terminal enomgogodla omine, kanye ne-terminal enomgogodla omihlanu.
Ngokwezinto zokufaka, ihlukaniswe kanje: ikhanda le-terminal yekhebula elincibilikayo elishisayo kanye nekhanda le-terminal yekhebula elincibilikayo elibandayo;

2.3.2 Ububanzi obusebenzayo besigaba esiphambene sekhebula

Igama Lomkhiqizo

Inombolo yomkhiqizo

Ingxenye yesiphambano sekhebula esebenzayo (mm²)

Itheminali yangaphakathi enezinsika ezine ebandayo engu-1kV

I-NLS-1/4.0

10~16

I-NLS-1/4.1

25~50

I-NLS-1/4.2

70~120

I-NLS-1/4.3

150~240

I-NLS-1/4.4

300~400

I-10kV cold shrinkled intermediate joint enezinsika ezintathu ebandayo

I-JLS-10/3.1

25~50

I-JLS-10/3.2

70~120

I-JLS-10/3.3

150~240

I-JLS-10/3.4

300~400

Itheminali yangaphandle engu-35kV eyodwa

I-WLS-35/1.1

50~95

I-WLS-35/1.2

120~240

I-WLS-35/1.3

300~400

I-WLS-35/1.4

500~800

Qaphela 1: Ishubhu yokuvikela yekhanda le-terminal ngokuvamile liyi-650mm ubude, kodwa lingandiswa libe yi-800mm, 1000mm, 1200mm ngokwezidingo zamakhasimende.

Inothi 2: Ikhanda le-terminal yekhebula le-XLPE lisebenzisa ubuchwepheshe bezintambo ezimbili zomhlaba, okungukuthi ucingo lomhlaba oluvikelwe kanye nocingo lomhlaba oluvikelwe ngethusi.

Inothi 3: Uma ubika izesekeli ze-intermediate joint, naka umbiko osekelayo: ibhokisi elingangeni manzi lekhebula kanye nebhokisi elingaqhumi.

2.3.3 Isixhumi se-plug yekhebula 1) Sisetshenziswa kabanzi ekuxhumeni ama-transformer ebhokisi, amabhokisi enethiwekhi yendandatho, amabhokisi amagatsha, ama-transformer agqitshwe kanye neminye imishini. Siyi-terminal ye-plug-in evalwe ngokuphelele futhi evalwe ngokuphelele.

2) Ukuhlukaniswa:
A. Ihlukaniswe yaba yi-plug head engu-10kV, i-plug head engu-20kV, i-plug head engu-35kV ngokwezinga le-voltage; B. Ihlukaniswe yaba yi-plug head yaseYurophu kanye ne-plug head yaseMelika. Ama-plug-in head esitayela saseYurophu ahlukaniswe: Isixhumi sangaphambili sesitayela saseYurophu, isixhumi sangemuva sesitayela saseYurophu, kanye ne-lightning arrester exhunywe ngemuva; isetshenziswa kabanzi ekuxhumeni amabhokisi enethiwekhi yendandatho, ama-transformer amabhokisi esitayela saseYurophu, kanye nemishini yamabhokisi egatsha lesitayela saseYurophu. Angama-terminal head e-plug-in agqunywe ngokuphelele futhi avaliwe ngokuphelele. Ikhebula kanye nemishini kuxhunywe nge-cable joint yohlobo loxhumano olune-bolt. Ama-plug head aseMelika ahlukaniswe yaba yi-: 200A American elbow head, 600A American III-generation T-head. Isetshenziswa kabanzi ekuxhumeni amabhokisi e-ring net aseMelika, ama-transformer amabhokisi aseMelika, kanye namabhokisi egatsha aseMelika. Kuyi-terminal e-plug-in egqunywe ngokuphelele futhi evaliwe ngokuphelele. Ukuxhumeka kwe-plug-in kwamukelwa phakathi kwekhebula nedivayisi.
Okwesithathu, ukukhethwa kwendawo yesendlalelo sokuvikela insimbi sekhebula le-polyethylene elixhunywe nge-cross-linked
3.1 Ukusekela isivikelo sensimbi
Ngokusho kwe-Athikili 4.1.10~4.1.11 ye-GB 50217-2018 Power Engineering Cable Design Standard: 4.1.10 Isikhwama sensimbi sekhebula lamandla kufanele sisekelwe ngqo. Isikhwama sensimbi sekhebula eliyi-3-core ohlelweni lwe-AC kufanele sisekelwe ngqo kuma-terminals amabili nasemajoyintini entambo yekhebula.
4.1.11 Igobolondo lensimbi lekhebula lamandla eliyi-AC elilodwa kufanele lisekelwe ngqo okungenani ekugcineni okukodwa, futhi inani eliphakeme lamandla ajwayelekile abangelwa kunoma yikuphi ukuphela okungasekelwe ngqo kufanele lihlangabezane nezidingo ezilandelayo:
1. Uma izinyathelo zokuphepha ezingavimbela ngempumelelo abasebenzi ukuthi bathinte isivikelo sensimbi ngokunganaki zingathathwa, i-voltage akufanele idlule ama-V angu-50;
2. Ngaphandle kwezimo ezichazwe esigabeni 1 salesi sihloko, akufanele kudlule ama-V angu-300;
3. Amandla ajwayelekile abangelwa yi-sheath yensimbi yekhebula eliyi-single-core yesistimu ye-AC kufanele abalwe ngokwefomula ekuSithasiselo F sale nqubo.
4.1.13 Uma ishelufu yensimbi yezintambo zamandla eziyinhloko eyodwa engaphansi kuka-35kV isekelwe ngqo endaweni eyodwa, futhi kunesidingo sokuvikelwa kokufakwa ...

3.2 Ukukhethwa kwendawo enqamula ingxenye yesendlalelo sokuvikela insimbi
Ngokusho kwe-Athikili 6.3.1 ye-DL/T401-2002 Iziqondiso Zokukhetha Ikhebula Elinamandla Aphezulu: Kwesendlalelo sokuvikela insimbi esivikelwe ngaphandle kwesihenqo sensimbi, lapho ingxenye yomqhubi ingu-240mm² nangaphansi, itheyiphu yethusi ingasetshenziswa ukuvikela, kodwa lapho ingxenye yomqhubi inkulu kuno-240mm² kufanele ivikelwe ngocingo lwethusi. Ingxenye yokuvikela yesivikelo sensimbi kufanele ihlangabezane nezidingo zesikhashana lapho kwenzeka iphutha lomhlabathi lesigaba esisodwa noma amaphutha amabili ngesikhathi esisodwa ezindaweni ezahlukene.